AC Current Transducer P/N: CINV/1

RANGE: IN: 0-1A AC, OUT: 4-20MA OUT POWER SOURCE: 110VAC, 50HZ APPLICATION: GENERATOR UNIT CONTROL PANEL (GUCP-1) OF ANSALDO G.T. GENERATOR NO. OF CT INPUTS: 01 CT INPUT: 500/1A AC AUX. SUPPLY: 110VAC/50Hz OUTPUT LOAD: 0-750OHM ACCURACY CLASS: 0.5 RIPPLE (Pk-Pk):

Description

RANGE: IN: 0-1A AC, OUT: 4-20MA OUT
POWER SOURCE: 110VAC, 50HZ
APPLICATION: GENERATOR UNIT CONTROL PANEL (GUCP-1) OF ANSALDO G.T. GENERATOR

NO. OF CT INPUTS: 01
CT INPUT: 500/1A AC
AUX. SUPPLY: 110VAC/50Hz
OUTPUT LOAD: 0-750OHM
ACCURACY CLASS: 0.5
RIPPLE (Pk-Pk): <1% RESPONSE TIME: < 0.15SEC VARIATION: < 1 PPM/OHM PROTECTION AGAINST SHORT CIRCUIT & OPEN CIRCUIT MOUNTING: DIN RAIL MOUNT IN COMPLIANCE WITH IEC 60688